Cable-to-rebar joints connect grounding cables to rebar embedded in concrete, using the rebar as part of the grounding system. Exothermic welding provides a secure, conductive bond that ensures electrical continuity within reinforced concrete structures, such as building foundations. This type of joint is widely used in construction and infrastructure projects to integrate grounding systems within concrete-reinforced buildings. The durable connection resists corrosion and ensures effective grounding, which is essential for electrical safety and stability in structures.
Rebar Size (Dia mm) | Cable Size mm2 | Mould | Weld Powder |
12 | 25 | CCL-1225 | 45 |
35 | CCL-1235 | 45 | |
50 | CCL-1250 | 90 | |
16 | 25 | CCL-1625 | 45 |
35 | CCL-1635 | 45 | |
50 | CCL-1650 | 90 | |
22 | 35 | CCL-2235 | 45 |
50 | CCL-2250 | 90 | |
70 | CCL-2270 | 90 | |
25 | 35 | CCL-2535 | 45 |
50 | CCL-2550 | 90 | |
70 | CCL-2570 | 90 | |
32 | 50 | CCL-3250 | 90 |
70 | CCL-3270 | 90 |